Air Pressure Transmitter PAM 1

Description

The PAM 1-Series Air Pressure Transmitters are designed for measuring differential pressure, volume flow, and both above-atmospheric and below-atmospheric pressures. These transmitters are ideal for clean room applications, medical and filter technologies, HVAC systems, spray booths, large-scale catering facilities, and more.

Equipped with multiple switchable pressure ranges and outputs, the PAM 1-Series provides flexibility and precision. It features a piezo-resistive, temperature-compensated measuring element, ensuring high reliability and accuracy. The device is available with or without an LCD display for real-time monitoring and includes a duct fixing kit for easy installation.

  • Features

    • Measuring Pressure Ranges:
      • PAM 10VC / PAM 10VC D: 0 to 50 Pa, -50 to +50 Pa, 0 to 100 Pa, -100 to +100 Pa.
      • PAM 11VC / PAM 11VC D: 0 to 100 Pa, -100 to +100 Pa, 0 to 300 Pa, -300 to +300 Pa, 0 to 500 Pa, -500 to +500 Pa, 0 to 1000 Pa, -1000 to +1000 Pa.
      • PAM 15VC / PAM 15VC D: 0 to 1000 Pa, -1000 to +1000 Pa, 0 to 2000 Pa, -2000 to +2000 Pa, 0 to 3000 Pa, -3000 to +3000 Pa, 0 to 5000 Pa, -5000 to +5000 Pa.
    • Output Signals: Switchable between 0-10 Vdc and 4-20 mA.
    • Manual Calibration: Pushbutton for zero-point calibration with adjustable offset.
    • LCD Display (Optional): Real-time display of pressure readings.
    • High Accuracy:
      • PAM 10VC and PAM 10VC D (100 Pa): ±3 Pa at 25°C.
      • PAM 11VC and PAM 11VC D (1000 Pa): ±10 Pa at 25°C.
      • PAM 15VC and PAM 15VC D (5000 Pa): ±35 Pa at 25°C.
    • Duct Fixing Kit Included: Includes 2 plastic tubes with integrated mounting plate, 2 meters of PVC hose, and 4 screws for secure installation.
    • Ingress Protection: IP67-rated enclosure for robust performance in demanding environments.
  • Application

    • Clean Rooms: Ensures precise pressure monitoring in controlled environments.
    • Medical Facilities: Suitable for pressure measurement in filter technology and ventilation systems.
    • HVAC Systems: Ideal for monitoring air ducts, spray booths, and catering facilities.
    • Filter Monitoring: Measures pressure to monitor filter performance and detect clogs.
    • Industrial Processes: Supports volume flow and level measurement.
  • Model

    PAM 10VC (without display) / PAM 10VC D (with display):

    • 4 pressure ranges:
      • 0 to 50 Pa, -50 to +50 Pa, 0 to 100 Pa, -100 to +100 Pa.

    PAM 11VC (without display) / PAM 11VC D (with display):

    • 8 pressure ranges:
      • 0 to 100 Pa, -100 to +100 Pa, 0 to 300 Pa, -300 to +300 Pa, 0 to 500 Pa, -500 to +500 Pa, 0 to 1000 Pa, -1000 to +1000 Pa.

    PAM 15VC (without display) / PAM 15VC D (with display):

    • 8 pressure ranges:
      • 0 to 1000 Pa, -1000 to +1000 Pa, 0 to 2000 Pa, -2000 to +2000 Pa, 0 to 3000 Pa, -3000 to +3000 Pa, 0 to 5000 Pa, -5000 to +5000 Pa.
  • Benefits

    • Flexibility: Multiple pressure ranges and output options ensure adaptability to various applications.
    • Precision: High accuracy and temperature-compensated measurements.
    • Ease of Use: Simple manual zero-point calibration and user-friendly installation.
    • Durability: IP67 protection for reliable operation in harsh environments.